Portable Generator QAS-125kW
General Information
The Atlas Copco QAS 125 JD T4F generators are prime power, multi-voltage, sound attenuated, mobile generators. They are powered by a John Deere T4 Final liquid-cooled, four-cylinder diesel engine.
The units consist of an alternator, diesel engine, cooling system, electrical distribution and control systems – all enclosed within a sound attenuated enclosure fabricated from powder coated steel with zinc rich primer. 6000 hour salt spray tested. A broad range of undercarriage formats and options are available. Special attention has been given to the overall product quality, user friendliness, ease of serviceability, and economical operation to ensure best in class total cost of ownership.
All QAS generators include the latest Tier 4 Final engine and have a footprint that is up to 20 percent smaller than the previous generation. The starting mechanism ensures that stable power is achieved in less than six seconds.
Rated Prime Power
100 kW / 125 kVA
Frequency
60 hz
Detailed Specs
- Compact, sound attenuated, corrosion resistant, with single point lifting and 110% fluid containment
- Available as a skid mounted unit with forklift pockets, or on a single axel trailer
- Heavy Duty alternator with AREP excilation and marine grade protection
- “DeepSea” controller
- Single side servicing with long run filters and 500 hour service intervals
- Extremely reliable and durable John Deere 4045 engine with DOC & SCR after-treatment and 5 year limited warranty
- Identical enclosures and maintenance points between both models
- Emergency Stop
- Remote Start / Stop
- Extremely durable and environmentally sensitive designed to be used for everything from the oil patch to special event power
- Versatility, giving you the flexibility to match your machine to the correct application
- Start-up power for the most demanding sites with 300% over load starting capabilites
- Reliable and intuitive controls for ease of use and diagnostic capabilities
- Heavy duty oil, air and fuel filters extend themaintenance interval to 500 hours for reduced total cost of ownership
- Reduces maintenance costs with long intervals easy access for mechanics
- Proven engine platform with high reliability, a simple maintenance free Diesel Oxidization Catalyst onlyafter treatment
- Reduces stock of service kits and inventory of parts withrental ROI kept in mind
- External, recessed emergency stop for increased safety
- Allows connection as a critical back-up unit via a 2 wire dry contact connection in the distribution panel
Performance | Units | QAS 125 |
Frequency | Hz | 60 |
Rated prime power 3ø | kW/kVA | 100/125 |
Rated standby power 3ø | kW/kVA | 110/138 |
3ø Power factor | 0.8 | |
3ø Voltage in 480V switch position | V | 480Y / 277 |
Amp capacity @480V | A | 150 |
3ø Voltage in 240-208V switch position | V | 240YY / 139-208YY |
Rated Prime Power @ 240V 3Ø | A | 100/125 |
Amp capacity @240V | A | 300.8 |
Rated Prime Power @ 2080V 3Ø | A | 86.5/108 |
Amp capacity @208V | A | 300 |
Rated prime power 1ø | kW/kVA | 65/65 |
1ø Power factor | 1 | |
1ø Voltage in 120-240V switch position | V | 240 / 120 |
Amp Capacity @240V | A | 271 |
Amp Capacity @120V | A | 271x 2 |
Main breaker – Rated Current in | A | 400 |
Power Distribution – Terminal Board | 5 Wire (L1, L2, L3, N, Ground) | |
Terminal Board Connections | Bare Wire Terminals | |
Maximum Terminal Cable Size | 350MCM | |
Convenience Receptacles | 2 x NEMA 5-20R & 2 x 125/250V 50A CS6364 | |
Max. sound pressure level (LPA) @23′ @75% Load | dB(A) | 73 |
Fuel and DEF Systems | Units | QAS 125 |
Fuel consumption at 100% load (PRP) | gal / h | 7.06 |
Fuel consumption at 75% load (PRP) | gal / h | 5.65 |
Fuel tank capacity | gal | 166 |
Fuel autonomy @75% load & 90% of fuel capacity | h | 166 |
DEF Tank Capacity | Gal (L) | 9.19 (34.8) |
Alternator | QAS 125 |
Model | Leroy Somer 44.3 S5 |
Excitation system | AREP (auxiliary winding) |
Automatic voltage regulator (+/-0.25%) | Leroy Somer D350 |
Insulation | Class H |
Engine | Units | QAS 125 |
Model | John Deere 4045 HFG04 | |
US EPA Family | HUDXL0.4.531 | |
US EPA Tier | Tier 4 Final | |
Displacement | L | 4.5 |
Cylinders | # | 4 |
Continuous engine output | HP | 157 |
Gross engine power output | HP | 172 |
Rated Speed | RPM | 1800 |
Engine control | ECU | |
Aspiration | Turbo w/ Intercooler | |
Engine oil capacity | US gal | 5.4 |
Engine coolant capacity | US gal | 2.25 |
Max. ambient temperature (@Sea Level) | °F | 122 |
Min. starting temperature (w/o Cold weather options) | °F | 14 |
Minimum starting temperature (w/Cold weather options) | °F | -13 |
Electrical system (Negative ground) | V | 12 |
Engine alternator output | A | 90 |
Battery Capacity (Cold Cranking Amps) | A | 1100 |